No. 30 Boiler Compound

No. 30 Boiler Compound

This product is a concentrated balanced boiler compound for treatment of steam boiler water. It is ideally suited for food plants and other industrial use. Test hardness of feed water. Hardness should not be higher than 200 ppm. If hardness exceeds 200 ppm, a separate softening procedure should be implemented. Estimate the amount of water in boiler. As a recommended initial treatment, add 1 gallon of product to each 200 gallons of water in the system. It is estimated that approximately 1 gallon of compound needs to be added to 500 gallons of make up water. This, however, will depend on the daily test results of the boiler water. The daily analysis of the boiler water should include alkalinity, pH and phosphate tests. Periodic analysis should also be done on the alkalinity of the feed water. p-alkalinity should be in the range of 200-400 ppm. m-alkalinity should be in the range of 400-800 ppm. pH should be in the range of 10-12. Phosphates (PO4) should be in the range of 30-50 ppm. Sulfite should be in the range of 20-40 ppm.